Article 210: Branch Circuits
From the Final Overcurrent Device to the Outlet
A branch circuit begins at the final overcurrent protective device and supplies outlets or electrical equipment. Article 210 covers branch-circuit ratings, required dwelling circuits, conductor loading, receptacle and lighting outlets, and GFCI and AFCI protection.
Article 210 is one of the most frequently used NEC articles because nearly every electrical installation contains branch circuits.

What Beginners Should Know
Circuit Ratings
Common branch-circuit ratings include 15, 20, 30, 40 and 50 amperes. The circuit rating must be coordinated with its conductors, overcurrent protection, receptacles and connected load.
Required Dwelling Circuits
The 2023 NEC requires certain 20-ampere branch circuits in dwelling units:
- At least two small-appliance circuits
- At least one laundry circuit
- At least one bathroom receptacle circuit
- At least one garage receptacle circuit, where applicable
Additional circuits may be required for cooking equipment, HVAC systems, dryers, water heaters and other loads.
Activity: Locate the Required Dwelling Circuits & AFCI Protection
AFCI AND GFCI PROTECTION
Article 220: Branch-Circuit, Feeder, and Service Load Calculations
Calculate Before You Install
Article 220 provides methods for calculating branch-circuit, feeder and service loads. These calculations help determine how much electrical capacity an installation needs.
Connected load and calculated load are not always the same. The NEC permits certain demand factors because some equipment is unlikely to operate at full capacity simultaneously. A demand factor may be used only when the applicable NEC rule permits it.
What Beginners Should Know
General Dwelling Load
For the 2023 NEC standard method, the dwelling-unit general load begins with the floor area multiplied by 3 volt-amperes per square foot.
NEC reference: 220.41
This calculation includes qualifying general lighting and general-use receptacle outlets.
Small-Appliance and Laundry Loads
Add 1,500 VA for each required small-appliance branch circuit and 1,500 VA for the required laundry circuit.
A dwelling requires at least:
- Two small-appliance circuits
- One laundry circuit
These loads are combined with the general floor-area load before applying the applicable dwelling demand factor.
Appliance Loads
Fastened-in-place appliances are generally calculated from their nameplate ratings.
When four or more qualifying appliances are supplied by the same feeder or service, a 75% demand factor may be permitted under 220.53.
This demand calculation excludes loads such as:
- Household cooking equipment
- Clothes dryers
- Space heating
- Air-conditioning equipment
- Electric vehicle supply equipment
Dryer and Cooking Loads
A household electric dryer is calculated at 5,000 VA or its nameplate rating, whichever is larger.
NEC reference: 220.54
Qualifying household electric ranges, ovens and cooking units are calculated using Table 220.55. The notes below the table are part of the calculation.
Heating and Cooling
Heating and cooling equipment that will not operate simultaneously may be treated as noncoincident loads. The applicable calculation generally includes the load that produces the larger result.
NEC reference: 220.60
Final Service Load
After all calculated loads are added, convert the total volt-amperes to amperes.
For a typical 120/240-volt, single-phase dwelling:
Amperes = Total volt-amperes ÷ 240 volts
The calculated result is then used to select service equipment, conductors and overcurrent protection.

220 Dwelling Load Calculation Activity

Article 230: Services
Where Utility Power Meets Premises Wiring
Article 230 covers the conductors and equipment that deliver electrical power from the serving utility to the premises wiring system.
It addresses overhead and underground services, service-entrance conductors, disconnecting means, equipment ratings, overcurrent protection, surge protection and service-equipment installation.

What Beginners Should Know
Article 240: Overcurrent Protection
Protecting Conductors Before Current Becomes Dangerous
Article 240 covers the selection, installation, and application of overcurrent protective devices such as circuit breakers and fuses. These devices open a circuit when excessive current threatens conductors or equipment.
A properly selected device must protect against excessive current while still allowing equipment to operate normally. Selecting a breaker from load alone is not enough—the load, conductor ampacity, equipment limitations, standard device ratings, and available fault current must work together.
Why Article 240 Matters
Excessive current creates heat. If the current exceeds what a conductor or piece of equipment can safely carry, insulation can deteriorate, connections can fail, and fire or equipment damage can result.
Article 240 helps electricians answer four questions:
- What is the calculated load?
- What ampacity must the conductors have?
- What size fuse or circuit breaker may protect them?
- Can the device safely interrupt the available fault current?
Understanding Overcurrent
“Overcurrent” includes several different conditions.

Article 250: Grounding and Bonding
Create an Effective Path for Fault Current
Article 250 addresses grounding and bonding. Although the terms are often used together, they serve different functions.
Grounding connects a system or equipment to earth. Bonding connects conductive parts together to establish electrical continuity and an effective ground-fault current path.
During a fault, the goal is not to send all fault current into the earth. The goal is to create a low-impedance metallic path that allows enough current to return to the source and operate the overcurrent protective device quickly.
Why Article 250 Matters
Grounding and bonding work together, but they do different jobs. Grounding connects the electrical system to earth to stabilize voltage and limit voltage caused by lightning, surges, or accidental contact with higher-voltage lines. Bonding connects conductive parts together to create a permanent, low-impedance path for ground-fault current. That fault-current path allows a fuse or circuit breaker to open quickly.
Critical principle: Earth is not an effective ground-fault current path. A fault must return to the source through an equipment grounding and bonding path with low enough impedance to operate the overcurrent protective device. See 250.4(A)(5).